Description
|
Part Number
|
Model
|
First supported version
|
NE9000-8 Integrated Chassis DC Components
|
02351PMJ
|
CR9PBKP08ADC
|
V800R010C00
|
NE9000-8 Integrated Chassis AC Components
|
02351PMK
|
CR9PBKP08AAC
|
V800R010C00
|
NE9000-8 Integrated 240V/380V HVDC Chassis Components
|
02351PYJ
|
CR9PBKP08AHC
|
V800R010C00
|
NE9000-8 Integrated AC/HVDC Chassis Components
|
02352RNN
|
CR9PBKP8AD00
|
V800R011C10
|
NE9000-8 Integrated DC Chassis Components B
|
02352SNE
|
CR9PBKP8DC00
|
V800R011C10
|
Item
|
Specification
|
Cabinet installation standards
|
Can be installed in an 1000 mm-deep standard 19-inch cabinet and is installed in a 2200 mm-high HW N610E cabinet by default.
|
Dimensions without packaging (H x W x D) [mm(in.)]
|
1016 mm x 442 mm x 945 mm (40 in. x 17.4 in. x 37.2 in.)
|
Dimensions with packaging (H x W x D) [mm(in.)]
|
1016 mm x 442 mm x 945 mm (40 in. x 17.4 in. x 37.2 in.)
|
Chassis height [U]
|
23 U
|
Weight without packaging [kg(lb)]
|
181 kg (399.0 lb)
|
Weight without packaging (full configuration) [kg(lb)]
|
374kg (824.5 lb)
|
Typical power consumption (with configuration) [W]
|
Typical 7970W (include 8 PMs, 3 LPU FANs, 2 SFU FANs)
|
|
2 MPU + 8 SFU + 8 20x100G QSFP28
|
|
Typical 13500W (include 9 PMs, 3 LPU FANs, 2 SFU FANs)
|
|
2 MPU + 8 SFU + 8 40x100G QSFP28
|
|
Typical 9079W (include 8 PMs, 3 LPU FANs, 2 SFU FANs)
|
|
2 MPU + 8 SFU + 20 20x100G QSFP28 (03058864)
|
Typical heat dissipation (with configuration) [BTU/hour]
|
25858 BTU/hour (include 8 PMs, 3 LPU FANs, 2 SFU FANs)
|
|
2 MPU + 8 SFU + 8 20x100G QSFP28
|
|
43799.7 BTU/hour (include 9 PMs, 3 LPU FANs, 2 SFU FANs)
|
|
2 MPU + 8 SFU + 8 40x100G QSFP28
|
|
29456.1 BTU/hour (include 8 PMs, 3 LPU FANs, 2 SFU FANs)
|
|
2 MPU + 8 SFU + 20 20x100G QSFP28 (03058864)
|
MTBF [year]
|
18.87 year
|
MTTR [hour]
|
0.5 hour
|
Availability
|
0.99999
|
Power supply mode
|
DC built-in
|
Maximum number of power chassis inputs
|
(8 channels/PEM)*3 PEM=(2 channels/PM)*4 PM*3 PEM=24 channels
|
Rated input voltage [V]
|
-48 V / -60 V
|
Input voltage range [V]
|
–40 V to –72 V
|
Maximum input current [A]
|
63 A/single-module
|
Maximum input cable size [mm²]
|
35 mm²/channel
|
Front-end circuit breaker/fuse [A]
|
2 channels of 63 A/single-module
|
|
[4T bundle] DC device: 6 PMs, with a total of 12 channels of 63 A
|
Noise at normal temperature (acoustic power) [dB(A)]
|
77.2dBA, NEBS-compliance (< 78 dBA @ 27°C)
|
Number of slots
|
18
|
Number of service board slots
|
8
|
Switching capacity
|
83.78 Tbit/s
|
Redundant MPUs
|
1:01
|
Redundant Switch fabrics
|
7+1
|
Redundant CMUs
|
1:01
|
Redundant power supply
|
[4T bundle] 5+1
|
Redundant fans
|
The device has two fan partitions. The LPU partition has three fan assemblies, which support 2+1 fan assembly redundancy. The SFU
partition has two fan assemblies, which support 1+1 fan assembly redundancy. |
Long-term operating temperature [°C(°F)]
|
0 °C ~ 40°C(32 °F ~ 104.0°F)
|
Short-term operating temperature [°C(°F)]
|
-5 °C ~ 50°C (23 °F ~ 122.0°F)
|
Storage temperature [°C(°F)]
|
-40 °C ~ 70 °C (-40.0°F ~ 158.0°F)
|
Long-term operating relative humidity [RH]
|
5% to 85%, non-condensing
|
Short-term operating relative humidity [RH]
|
5% to 95% RH, non-condensing
|
Storage relative humidity [RH]
|
5% to 95% RH, non-condensing
|
Long-term operating altitude [m(ft.)]
|
≤ 4000 m (13123.2 ft.) (For the altitude in the range of 1800 m to 4000 m [5905.44 ft. to 13123.2 ft.], the operating temperature
of the device decreases by 1°C [33.8°F] each time the altitude increases by 220 m [721.78 ft.].) |
Storage altitude [m(ft.)]
|
< 5000 m (16404.2 ft.)
|