Description
|
Part Number
|
Model
|
First supported version
|
Remarks
|
NE5000E-20 Integrated Chassis and Cabinet DC Components (include chassis and power distribution frame)
|
02353BSP
|
CR5B0BKP206C
|
V800R011C10
|
Including chassis (02351VYV) and power shelf (02312NSH)
|
NE5000E-20 Integrated Chassis and Cabinet AC and HVDC Components(include chassis and power distribution frame)
|
02353BSS
|
CR5B0BKP206D
|
V800R011C10
|
Including chassis (02351WBJ) and power shelf (02312LWQ)
|
|
|
|
|
|
Item
|
Specification
|
Cabinet installation standards
|
Integrated chassis and cabinet (with acoustic doors)
|
Dimensions without packaging (H x W x D) [mm(in.)]
|
2200 mm x 600 mm x 1000 mm (86.61 in. x 23.62 in. x 39.4 in.)
|
Chassis height [U]
|
49.5 U
|
Weight without packaging [kg(lb)]
|
440 kg(970.04 lb)
|
Weight without packaging (full configuration) [kg(lb)]
|
1.6T single-chassis (full configuration 100GE): 830.9 kg (1832.12 lb)
|
|
1.6T cluster (full configuration 100GE): 852.5 kg (1879.75 lb)
|
Typical power consumption (with configuration) [W]
|
1.6T single-chassis: 27030 W(2*MPU + 2*CMU + 8*SFU1T6D + 20*16*100GE + 8*FAN2.0 + 2*FAN)
|
|
1.6T cluster: 29610 W(2*MPU + 2*CMU + 8*SFUI1T6H + 20*16*100GE + 8*FAN2.0 + 2*FAN)
|
Typical heat dissipation (with configuration) [BTU/hour]
|
1.6T single-chassis: 87696.7 BTU/hour (2*MPU + 2*CMU + 8*SFU1T6D + 20*16*100GE + 8*FAN2.0 + 2*FAN)
|
|
1.6T cluster: 96067.3 BTU/hour (2*MPU + 2*CMU + 8*SFUI1T6H + 20*16*100GE + 8*FAN2.0 + 2*FAN)
|
MTBF [year]
|
14.88 year
|
MTTR [hour]
|
0.5 hour
|
Availability
|
0.99999
|
Power supply mode
|
DC built-in
|
Maximum number of power chassis inputs
|
(8 channels/PEM)*6 PEM=(2 channels/PM)*6 PM*4 PEM=48 channels
|
Rated input voltage [V]
|
-48 V /-60 V
|
Input voltage range [V]
|
–40 V to –72 V
|
Maximum input current [A]
|
63 A/single-module
|
Maximum input cable size [mm²]
|
35 mm²/channel
|
Front-end circuit breaker/fuse [A]
|
2 channels of 63 A/single-module
|
Heat dissipation mode
|
I-shaped air channel
|
Airflow direction
|
From front to back
|
Number of slots
|
32
|
Number of service board slots
|
20
|
Switching capacity
|
248.2 Tbit/s
|
Redundant MPUs
|
1:01
|
Redundant Switch fabrics
|
7+1
|
Redundant CMUs
|
1:01
|
Redundant power supply
|
N+1
|
Redundant fans
|
The fan modules are distributed into the SFU area and the LPU area.
|
|
The fan modules in the SFU area are located in the middle of the rear side of the chassis. There are two fan modules in total on
the left and right sides of the chassis. The device can work properly for a short time at 40ºC if a single fan module fails. |
|
The fan modules in the LPU area are located in the upper and lower areas at the rear of the chassis. Each area has four fan
modules. For each area, the device can work properly for a short time at 40ºC if a single fan module fails. |
Long-term operating temperature [°C(°F)]
|
0°C to 40°C(32°F to 104°F)
|
Short-term operating temperature [°C(°F)]
|
-5°C to 50 °C(23°F to 122°F)
|
Restriction on the operating temperature variation rate [°C(°F)]
|
≤ 30 °C/hour (54°F/hour)
|
Storage temperature [°C(°F)]
|
–40°C to +70°C (–40°F to +158 °F)
|
Long-term operating relative humidity [RH]
|
5% RH to 85% RH, non-condensing
|
Short-term operating relative humidity [RH]
|
5% RH to 95% RH, non-condensing
|
Storage relative humidity [RH]
|
5% RH to 95% RH, non-condensing
|
Long-term operating altitude [m(ft.)]
|
≤ 4000 m (13123.2 ft.) (For the altitude in the range of 1800 m to 4000 m [5905.44 ft. to 13123.2 ft.], the operating temperature
of the device must decrease by 1°C [33.8°F] for every 220 m [721.78 ft.].) |
Storage altitude [m(ft.)]
|
Less than 5000 m (16404 ft.)
|
Email: Lilicheng0510@163.com